Time relay 8A - Crouzet MUR3

Crouzet

More info

Crouzet MUR3 - Time relay 8 has

 

Crouzet MUR3 - Time relay 8 has

 

› Multifunction or monofonction
› Downtime (7 ranges switchable)
› Multivoltage
› Screw or spring terminals
› Visualization of States led 1 (relay version) › possibility to supply a load in parallel › possible order by sensor 3 son


Dimensions

 

Dimensions


Output 1 relay inverter

 

 

Output 1 relay inverter


Features

 

Features

 

Specifications
FunctionsA Ac - At - B - Bw - C - D - Di - H - Ht
Time delay0,1s →100 h
Output1 relay inverter
Rated current8A
ConnectionsScrew terminals
Supply voltage12 →240 V∿/⎓
Reference88827103
Time delay
Delay lines (7 lines)1 s - 10 s - 1 min - 10 min - 1 h - 10 h - 100 h
Fidelity of repetition (at constant parameters)± 0.5% IEC / EN 61812-1
Drift in temperature± 0.05% / ° C
Drift in tension± 0.2% / V
Accuracy of display according to IEC / EN 61812-1± 10% / 25 ° C
Immunity to the popping time: typical< 10 ms
Minimum length of the typical pulse (relay version)30 ms
Minimum length of the typical pulse (static version)50 ms
Minimum length of the typical pulse (with load relay version)100 ms
Time to maximum rearmament by typical power failure (relay version)120 ms
Time to maximum rearmament by cutting typical supply (static version)350 ms
Power
Multivoltage supply voltageAccording to version
Frequency (Hz)50/60
Market factor100.00%
Range of use85% →110
85% a for 12 V ∿/⎓ →120
Power consumption maximum32 GO (240 V∿) - 1.5 W (240 V⎓) - 0.6 W (24 V⎓) - 0.7 WILL (12 V∿) - 0.7 W (12 V⎓)
Output items
Breaking capacity2000 / 80 W
Maximum breaking current8 A∿ 250 V∿ resistive - 8 A⎓ 30 V⎓ resistive
Minimum breaking current10 my / 5 V⎓
Maximum cut-off voltage250 V∿ / 8 A∿ resistive 250 V⎓ / 0.3 A resistive
Life time electric (maneuvers)10⁵
250 V∿ resistive 8A
Life mechanics (maneuvers)10 x 10⁶
Dielectric strength according to IEC / EN 61812-12.5 kV / 1 min / 1 my / 50 Hz
Surge according to IEC / EN 60664-1, IEC / EN 61812-15 kV - wave 1.2/50 μs
General characteristics
Compliance with standardsIEC / EN 61812-1, IEC / 61000-6-1, IEC / 61000-6-2, IEC / 61000-6-3, IEC / 61000-6-4
CertificationsCE, UL, ass, CSA, GL
Temperature limits use (° C)-20 → + 60
Temperatures (° C) storage limit-30 → + 60
Installation category (according to IEC / EN 60664-1)Category of overvoltage III
Creepage and distance in the air according to IEC / EN 60664-14 kV / 3 mm
Degree of protection (IEC / EN 60529)IP20
 IP40
Degree of protection (IEC / EN 60529) frontIP50
Held in vibration according to IEC / EN 60068-2-620 m/s² 10 Hz →150 Hz
Relative humidity according to IEC / EN 60068-2-30 without condensation93% without condensation
Electromagnetic compatibility - immunity to landfills TIC-ticks according to IEC / EN 61000-4-2Level III (Air 8 kV/6 kV contact)
Immunity to electromagnetic fields according to IEC / EN 61000-4-3Level I - (1 V/m: 2.0 G round ' 2.7 G Hz Hz) level II - (3 V/m: 1.4 G Hz →2, 0 G Hz) level III - (10 V/m: 80 M Hz →1 G Hz)
Immunity to rapid transient burst according to IEC / EN 61000-4-4Level III (live 2 kV/clamp coupling capacitive 1kV)
Immunity to surges on supply according to IEC / EN 61000-4-5Level III (mode common 2 kV / 1 kV differential mode)
Immunity to the frequency in common mode according to IEC / EN 61000-4-6Level III (effective 10V: 0.15 M to 80 M Hz Hz)
Immunity to the hollow and cuts voltage according to IEC / EN 61000-4-110% residual voltage, 1 cycle
70% residual voltage, 25-30 cycles
Conducted emissions sector and radiated according to EN 55022 (CISPR22), EN55011 (CISPR11)Class B
Setting: symmetrical DIN rail35 mm
Ability of Muskie clamping without tip1 x 0.5 →3, 3 mm² - (AWG 20 →AWG 12) 2 x 0.5 →2, 5 mm² - (AWG 20 →AWG 14)
Capacity clamping multilegged with tip1 x 0.5 →2, 5 mm² - (AWG 20 →AWG 14) 2 x 0.5 →1, 5 mm² - (AWG 20 →AWG 16)
Case materialSelf-extinguishing.
Test shock according to IEC / EN 60068-2-2715 g - 11 ms
Short interruptions of voltage according to IEC / EN 61000-4-110% residual voltage, 250/300 cycles
Terminals with spring, 2 terminals by connecting point - flexible son2 x 0.5 →1, 5 mm² - (AWG 20 →AWG 16)
Terminals with spring, 2 terminals by connecting point - rigid son2 x 0.5 →1, 5 mm² - (AWG 20 →AWG 16)
Mass: 17.5 mm casing88827105 (MUR1): 63 g 88827115 (MAR1): 63 g 88827125 (MBR1): 63 g 88827135 (MCR1): 62 g 88827145 (MHR1): 63 g 88827150 (MLR4): 63 g 88827155 (MLR1): 64 g 88827100 (MUR4): 62 g 88827103 (MUR3): 66 g 88827503 (MURc3): 59 g
Insulation according to IEC / EN 60664-1100 MΩ (500 V ⎓)
Output element
Relay 1 or 2 inverters AgNi (without cadmium)1 C/O