External Enwitech protection box for SolarEdge View full size

External Enwitech protection box for SolarEdge

SolarEdge

Options

The "NL/BE" external protection cabinet should be used exclusively in configuration with a SolarEdge "StorEdge" single-phase inverter with "SE5000-RWS" Backup function.
The external protective cabinet, the components used and the electrical wiring were tested and approved by the manufacturer SolarEdge.

More details

More info

"External protection box for SolarEdge "StorEdge"

 

 

Application: "StorEdge" Backup System - SolarEdge
PV/battery-compatible inverter: StorEdge SE5000-RWS
Earth-linking scheme: TT or TN-S scheme; 1ph or 3ph (230/400V 50Hz) Connection: 1ph (230V/N)
Separation of the network: All poles


Size 

Size


Technical data

 

Characteristics
Rated tension AC [V]1ph -230 (L/N)
Public network/building connection [V]1AC or 3AC 230/400
Isolation nominal tension [V] 400
Frequency of operation [Hz] 50
Switchable short-circuit current max. [kA] 10
Authorized land link scheme (customer system) TT/TN-S
Earth-linking scheme in Backup modeTN-S
Phase coupling (Backup mode) (impossible)
Maximum consumer power allowed [kW] 4.5 (7 short-term - 300s)
Maximum crossing thermal power [kW]12 (consumers - inverter)
Losses on standby [W]about 7
General data
Dimensions (LxHxP) [mm]448x432x161
Weight [kg]10
Operating temperature range [C]-20..40
Transport/storage temperature [C]-25..-55
Short-term maximum 24 hours [C] -25..-60
Condenser moistureX
Humidity - permissible range [%] 5 ... 95
Maximum installation altitude above sea level [m]2000
IP Protection Index (EN 60529) 65
Outdoor installation X
Type of installation Inside
Protective class (EN 61140)
Case materialPolycarbonate
RoHS Compliance (2011/65/EU)
Case colourSimilar to RAL7046
Type of assemblyWall mounting
CoverTransparent
Type of closure (actuation)Without tools
Standards/Standards
Set of equipment61439-1
61439-2
61439-3
Stationary electrical energy storage systemsVDE-AR-E 2510-2
Other
Tariff number 85371098