SolarEdge Modbus Meter
More info
Energy meter with Modbus connection suitable for installations
SolarEdge
• High accuracy meter readings (up to 0.5%) for production/consumption readings
• Limitation of the export of production to the network
• Small in size and easy to install - suitable for standard electrical cabinets
• Suitable for residential, tertiary and ground farm installations
• Compatible with RS485 end-of-line resistors at 120 Ohms
ELECTRICAL DATA | ||
Operating voltage range - phase to neutral, phase to phase | Vac | Nominal: 230/400 184-264.5 / 320-460 |
AC Frequency | Hz | 45 / 65 |
Supported networks - single-phase; Phase* | L / N / PE ; L1 / L 2 / L3 / N / PE | |
Power consumption (norm) | W | 3 |
TC inputs | Mv | 333 |
COMMUNICATION | ||
Supported communication interfaces | RS485 half-duplex, 3-wire (A, B, GND) | |
Response time | dry | ≤200 |
Default device identification (Modbus) | 2 | |
End of line resistor | RS485 at 120 Ohms | |
PRECISION (@25°C, PF:0.7- 1)(5) | ||
5% - 100% of rated TC current | % | ±1.0 |
IEC accuracy | IEC 62053-21 Class 1, IEC 62053-23 Class 2 | |
COMPLIANCE | ||
Security | IEC 61010-1, UL 61010-1, CAN/CSA-C22.2 No. 61010-1-04 | |
Immunity | EN 61326: 2000, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6,EN 61000-4-5, EN 61000-4-6, | |
Emissions | EN 55022 Class B | |
INSTALLATION SPECIFICATIONS | ||
Dimension (HxWxW) | mm | 75 x 138.6 x 35 |
Weight | g | 0.2 |
Enclosure Type | °C | -40 to +85 |
Operating temperature range | 5% to 90% up to 40°C decreasing linearity to 50% RH at 55°C | |
Relative humidity (non-condensing) | IP20 - Suitable for indoor use | |
Type of assembly | DIN rail / Surface mount |
Data sheets and documentation
Specifications
1 MPPT |